Protection relays UTX line
UTX universal devices ensure swift, selective and reliable fault clearance in case of any type of short circuits. Full range of types of universal terminals UTX is used to protect the fields working with the neutral point in any configuration. Suitable types of protection relays are intended to operate in the following CB bays: feeding bay, feeding HV/MV power transformer, auxiliary voltage MV/LV transformer, overhead line, underground cable, capacitor bank, bus coupler, VT section, breaker failure protection and busbar protection. Reliability of the protection mechanism is ensured by the precise and quick measurement of short-circuit impedance. The UTX protection relays can calculate the distance to the location where the short circuit occurred.
The most important additional functionality of 3rd series compared to the 2nd series is the implementation of the IEC 61850 protocol. In addition UTX 3rd series has a revised front-panel (display, keyboard) and is equipped with the relay PAX package (package of 4 powerful and quick exits) as a standard.
The devices are equipped with A/C transducers. As a standard, they are equipped with network transmission interfaces Ethernet and TCP/IP and optionally fibre optic communication interfaces for TRbus, AAbus and IEC 870-5-103 protocols.
Optionally, the serial transmission interface of CCBus engineering channel may be lead out to the device front panel. The devices can be equipped with CANBus interface (2 channels) for a superior system. Moreover, UTX line series 2 cooperate with Xserver concentrator, which may be implemented with DNP3.0 protocol.
No. | Type | Functionality | |
1 | UTXvZRP | UTXvZRP series 3 | UTXvZRP series 2 |
Universal distance, differential, overcurrent and earth fault protection relay | 37, 37BC, 23/26, 81U, 81O, 21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 68, 21SOTF/50SOTF, 94,87LP, 85-21/85-87LP/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF, 62. |
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 68, 21SOTF/50SOTF, 94,87LP, 85-21/85-87LP/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF, 62. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. | ||
2 | UTXvZ | UTXvZ series 3 | UTXvZ series 2 |
Universal distance, overcurrent and earth fault protection relay | 37, 37BC, 23/26, 81U, 81O, 21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 21SOTF/50SOTF, 94, 68, 62, 85-21/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
21Z/21ZN, 21GC, 21FL, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 21SOTF/50SOTF, 94, 68, 62, 85-21/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
||
3 | UTXvRP | UTXvRP series 3 | UTXvRP series 2 |
Universal differential, overcurrent and earth fault protection relay | 37, 37BC, 23/26, 81U, 81O, 21GC, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 21SOTF/50SOTF, 62, 87LP, 85-87LP/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
21GC, 25, 50/51/67, 59, 27, 49, 32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 21SOTF/50SOTF, 62, 87LP, 85-87LP/77/68, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. | ||
4 | UTXvD | UTXvD series 3 | UTXvD series 2 |
Universal overcurrent and earth fault protection relay | 37, 37BC, 23/26, 81U, 81O, 21GC, 25, 50/51/67, 59, 27, 49,32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
21GC, 25, 50/51/67, 59, 27, 49,32, 46, 47, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
||
5 | UTXvS | UTXvS series 3 | UTXvS series 2 |
Universal earth fault protection relay | 37, 37BC, 23/26, 81U, 81O, 21GC, 49, 32, 46, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF. HMI, DFR, SER, PMU, CLK, TCM, LGC, VTFF. |
21GC, 49, 32, 46, 50N/51N, 67N, 50H(2), 50BF, 79, 74, 94, 62, 64, 21SOTF/50SOTF. HMI, DFR, SER, PMU, CLK, TCM, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
||
6 | UTXvTR | UTXvTR series 3 | UTXvTR series 2 |
Universal differential power transformer protection relay | 23/26, 87T, 50/51/67, 50H(2), 50H(5), 50BF, 74, 62. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC. |
87T, 50/51/67, 50H(2), 50H(5), 50BF, 74, 62. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. | ||
7 | UTXvL | UTXvL series 3 | UTXvL series 2 |
Universal protection relay for a line with the neutral point in any configuration. | 37, 25, 37BC, 23/26, 81U, 81O, 50/51/67, 59, 27, 49, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G,50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
50/51/67, 59, 27, 49, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G,50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, |
||
8 | UTXvMSZ+(LRW) | UTXvMSZ+(LRW) series 3 | |
Universal busbar protection relay and circuit -breaker failure protection |
50BF, 74, HMI, DFR, SER, PMU, CLK, LGC, MET. | ||
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
|||
9 | UTXvMSZ | UTXvMSZ series 3 | |
Universal busbar protection relay | 74, HMI, DFR, SER, PMU, CLK, LGC. | ||
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
|||
10 | UTXvLRW | UTXvLRW series 3 | |
Universal circuit -breaker failure protection |
50BF, 74, HMI, DFR, SER, PMU, CLK, LGC, MET. | ||
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
|||
11 | UTXvMR | UTXvMR series 3 | |
Universal differential protection relay of line with branches | 87, 74, HMI, DFR, SER, PMU, CLK, LGC, MET. | ||
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
|||
12 | UTXvP | UTXvP series 3 | UTXvP series 2 |
Universal VT bay protection relay | 23/26, 81U, 81O, 59, 27, 46, 47, 59N, 81U/81O, 74, 62, 64. HMI, DFR, SER, PMU, CLK, MET, LGC, VTFF. |
59, 27, 46, 47, 59N, 81U/81O, 74, 62, 64. HMI, DFR, SER, PMU, CLK, MET, LGC, VTFF. |
|
IEC 61850, XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. |
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS, DiffChannel TRbus. | ||
13 | UTXvA | UTXvA series 2 | |
Universal autonomous protection relay for HV or MV bay | 50/51/67, 59, 27, 32, 90Q, 41N, 90C, 46, 47, 50N/51N, 59N, 67N, 21YN, 21YNR, 64G, 50H(2), 50BF, 81U/81O, 79-81O, 79, 74, 50SOTF, 94, 68, 62, 64. HMI, DFR, SER, PMU, CLK, TCM, MET, LGC, VTFF. |
||
XMD CCbus, Alice’79 AAbus, IEC 60870-5-103, PPM2 CANBUS. |
Computers & Control Company reserves the right to change the above mentioned parameters.
Attention! DNP3.0 protocol is available through the cooperation with Xserver.
No. | ANSI code | Description |
1 | 50/51/67 | Phase directional overcurrent protection relay |
2 | 37 | Undercurrent protection relay (non-directional ) |
3 | 50N/51N | Non-directional earth fault Ie protection relay |
4 | 67N | Directional earth fault IEk protection relay |
5 | 21Z/21ZN | Distance protection relay |
6 | 68 | Power swing detection |
7 | 21FL | Fault locator |
8 | 85-21/77/68 | Universal teleprotection interface for distance protection relay |
9 | 85-87LP/77/68 | Universal teleprotection interface for differential protection relay |
10 | 87LP | Differential protection relay |
11 | 64 | Ground detector relay |
12 | 79 | Reclosing relay |
13 | 25 | Synchronism-check relay |
14 | 49 | Thermal relay (thermal model) |
15 | 23/26 | Temperature control device |
16 | 59 | Overvoltage relay |
17 | 27 | Undervoltage relay |
18 | 32 | Directional power relay |
19 | 59N | Overvoltage earth fault UE relay |
20 | 21YN | Admittance earth fault YE relay |
21 | 37 | Incremental admittance earth fault YE relay |
22 | 21YNR | Overcurrent Ig protection relay |
23 | 81U | Underfrequency f< protection relay |
24 | 81O | Overfrequency f> protection relay |
25 | 81U/81O | Load shedding protection relay LS |
26 | 79-81O | Auto recloser after load shedding (AR/LS) |
27 | 90Q | Automatic power factor correction |
28 | 41N | Automatic force of power active component |
29 | 90C | Capacitor banks control |
30 | 50H(2) | 2nd harmonic detection in phase currents |
31 | 50H(5) | 5nd harmonic detection in phase currents |
32 | 37 | Current fall signalling |
33 | 46 | Current asymmetry signalling |
34 | 47 | Voltage asymmetry signalling |
35 | 37BC | Open circuit detector |
36 | 50BF | Circuit breaker-failure protection |
37 | 74 | Signalization AW, AL, UP |
38 | 21GC | Parallel line compensation |
39 | 81R | Rate of change of frequency df/dt |
40 | 81R | Change of frequency delta f/ delta t |
41 | 37 | Reverse phase sequence detection |
42 | 47 | Switch-off cooperation circuits (“pumping” lock) |
43 | 62 | Operation time-delay of protection relay |
44 | SOTF | Switch on to fault |
45 | 21SOTF | Switch on to fault protection |
46 | 50SOTF | Switch on to fault protection |
47 | VTFF | VT fuse fail |
48 | HMI | LCD bay terminal screen with real-time displaying |
49 | DDR | Dynamic disturbance recorder |
50 | DFR | Digital fault recorder |
51 | TCM | Trip circuit monitor |
52 | LGC | Logic functions |
53 | MET | Amps, volts, watts, vars, power factor, energy metering. |
54 | PMU | Synchronous sampling analog inputs |
55 | CLK | Time synchronization and real-time clock |
56 | SER | Events recorder (log), reporting of short-circuit current break off |
57 | 87T | Differential protection of transformer |